<th id="m4sxs"></th>
    1. <th id="m4sxs"></th>

      <strong id="m4sxs"><form id="m4sxs"></form></strong>

      <code id="m4sxs"><abbr id="m4sxs"></abbr></code>
    2. <b id="m4sxs"><menuitem id="m4sxs"></menuitem></b>

    3. <kbd id="m4sxs"></kbd>
        RS485 Access Control Board Communication Problem
        2016-11-10 13:31
        Details of the problem:

        We used your 132 sets of RS485 access control boards, using two FC-08 converters, divided into two buses, the first has 103 access control boards, the second has 29, when connecting for communication, it was found that 29 devices on the second bus could not communicate, there is a communication indicator light next to the communication ports of all boards, it is different from the normal time, what is the problem?

        Expert answer:

        Hello, if the communication indicator RX light is always on, it means that your RS485 is connected to A and B incorrectly, that is to say, the A of a device in your bus is connected to B, and B is connected to A, which is wrong. Please check the line to find the wrong device and connect it back in the correct way.

        The following provides a set of error exclusion tables for reference

        Stephanie Stephanie Stephanie Ellie Ellie Ellie Victoria Victoria Victoria Olivia Olivia Olivia Isabella Isabella Isabella Jayden Jayden Jayden Lucas Lucas Lucas Dylan Dylan Dylan Ryan Ryan Ryan Noah Noah Noah

        Sweep the concern Yingze electronic official WeChat

        x
        Sample Apply
        ※ Please fill in your information, our company will deal with your problem as soon as possible.
        <th id="m4sxs"></th>
          1. <th id="m4sxs"></th>

            <strong id="m4sxs"><form id="m4sxs"></form></strong>

            <code id="m4sxs"><abbr id="m4sxs"></abbr></code>
          2. <b id="m4sxs"><menuitem id="m4sxs"></menuitem></b>

          3. <kbd id="m4sxs"></kbd>
              国产成人无码精品亚洲 | 一级黄色电影大全 | 成人性爱网址 | 大吊操色逼 | 俺也去官网,国产97碰公开 |